ICS Triplex T8403 为每个输入通道独立配置 您所在的位置:网站首页 input application关闭 ICS Triplex T8403 为每个输入通道独立配置

ICS Triplex T8403 为每个输入通道独立配置

2023-04-06 06:32| 来源: 网络整理| 查看: 265

原标题:ICS Triplex T8403 为每个输入通道独立配置

当线路监控设备安装在现场开关处时,该模块可以检测现场电缆的开路和短路。线路监控功能

为每个输入通道独立配置。

该模块通过

分辨率为1ms。状态的改变会触发一个SOE条目。州是

由每个通道上可以配置的电压阈值确定

原因

状态指示灯

模块前面板上有输入通道状态指示灯,每个指示灯一个

字段输入。输入状态LED模式取决于电压电平

现场I/O信号的。测量每个场输入电压,并将其与

六个阈值级别(四个可配置,两个固定),产生七个

阈值频带,如第8节所述。每个阈值带可以是

定义为具有特定的指示器模式:关闭、绿色、红色、闪烁的绿色,

或闪烁红色。

可配置的电压阈值和LED模式允许用户

自定义输入测量和状态指示,以适合个人

应用程序要求。在没有自定义的情况下,默认指示器

模式适用于没有线路监控的数字输入,并且是:

指示器状态描述

绿色

绿色–闪烁

红色–闪烁

打开现场开关(触点)

闭合磁场开关(触点)

展开全文

相关通道输入电压超出范围(即

低于最低跳闸阈值或高于最高跳闸阈值)

相关通道故障

The module can detect open and short-circuit field cables when a linemonitoring device is installed at the field switch. Line monitoring functions

are independently configured for each input channel.

The module provides on-board sequence of events (SOE) reporting with a

resolution of 1ms. A change of state triggers an SOE entry. States are

determined by voltage thresholds that can be configured on a per channel

basis.

Status LEDs

There are input channel status LEDs on the module front panel, one for each

field input. The input status LED mode is dependent upon the voltage level

of the field I/O signal. Each field input voltage is measured and compared to

six threshold levels (four configurable and two fixed) which produce seven

threshold bands, as described in Section 8. Each threshold band can be

defined to have a particular indicator mode: off, green, red, flashing green,

or flashing red.

The configurable voltage thresholds and LED modes allow users to

customize the input measurement and status indications to suit individual

application requirements. Without customization, the default indicator

modes are suitable for digital inputs without line monitoring and are:

Indicator State Description

Off

Green

Green – flashing

Red – flashing

Open field switch (contact)

Closed field switch (contact)

Associated channel input voltage out of range (i.e., either

below the lowest trip threshold or above the highest)

Associated channel faulty返回搜狐,查看更多